Xnx Universal Transmitter Quick Start Guide 🆒

: The XNX is certified for worldwide use in hazardous environments. For explosion-proof integrity, the cover must be fully seated with at least 9 threads engaged , and conduit runs must have a seal fitting within 18 inches (45cm). Wiring and Power Specifications

Apply the magnetic wand to to accept the new zero point. Step 2: Span Calibration Select Span Calibration from the menu. Xnx Universal Transmitter Quick Start Guide

The Xnx Universal Transmitter supports 24 VDC (nominal, 18-30 VDC) and can be configured for 3-wire (power, ground, signal) or 2-wire (loop-powered) operation. This guide covers the common 3-wire 4-20mA setup. : The XNX is certified for worldwide use

Regular calibration is critical to maintaining safety and accuracy. Ensure you have the correct calibration gas cylinder, a fixed-flow regulator (0.5 L/min standard), and the XNX calibration adapter. Step 1: Access the Calibration Menu Step 2: Span Calibration Select Span Calibration from

: Wait for the display countdown to finish (typically 3–5 minutes).

The physical placement of your Xnx transmitter directly impacts its performance.

Danger: Ensure all power to the circuit is disconnected before opening the enclosure or making wiring terminations in hazardous locations. Enclosure Entry